This tab serves following purposes:
 
This tab serves following purposes:
 
* Connecting and disconnecting to a drive
 
* Connecting and disconnecting to a drive
Line 12: Line 12:
  
 
Minimum requirements for connection:
 
Minimum requirements for connection:
* [[Argon (servo drive)]]  
+
* [[Argon]] or [[IONI]] motor drives
 
* 24VDC regulated power supply
 
* 24VDC regulated power supply
 
* [[SimpleMotion V2 compatible communication interface device]] (such as [[SimpleMotion V2 USB adapter]])
 
* [[SimpleMotion V2 compatible communication interface device]] (such as [[SimpleMotion V2 USB adapter]])
Line 18: Line 18:
  
 
===Establishing connection===
 
===Establishing connection===
 +
====Argon====
 
# Connect PE of [[Argon_wiring#J3_24V_power_and_motor_brake_port|J4 connector]] to protective earth. After that wire 24 VDC power supply to Argon's [[Argon_wiring#J3_24V_power_and_motor_brake_port|J3 connector]], however do not power up yet.
 
# Connect PE of [[Argon_wiring#J3_24V_power_and_motor_brake_port|J4 connector]] to protective earth. After that wire 24 VDC power supply to Argon's [[Argon_wiring#J3_24V_power_and_motor_brake_port|J3 connector]], however do not power up yet.
 
# [[Setting device bus address|Set drive address]] to give an bus address to the device.
 
# [[Setting device bus address|Set drive address]] to give an bus address to the device.
# Connect Argon J2.1 connector to [[SimpleMotion V2 USB adapter]] with a straight Ethernet cable and plug USB adapter to computer.
+
# Connect Argon J2 (any of two ports) connector to [[SimpleMotion V2 USB adapter]] with a straight Ethernet cable and plug USB adapter to computer.
 
# Power up the 24 VDC power. Some leds should start blinking at the drive (specifily LD3 and/or LD4).
 
# Power up the 24 VDC power. Some leds should start blinking at the drive (specifily LD3 and/or LD4).
 
# Launch Granity software and:
 
# Launch Granity software and:
 
##Go to Connect tab
 
##Go to Connect tab
##Ensure that SM V2 USB adapter is selected from drowdown list called ''Communication interface device''
+
##Ensure that SM V2 USB adapter is selected from dropdown list called ''Communication interface device''
 +
##Click ''Connect to drive''
 +
##Once list of connected drives pop up, select the one you connected and click ''Open''
 +
====IONICUBE====
 +
# Wire up IONICUBE logic power (24V) supply.
 +
# Connect IONICUBE connector X1 (any of two ports) connector to [[SimpleMotion V2 USB adapter]] with a straight Ethernet cable and plug USB adapter to  computer.
 +
#Make sure that SM bus termination is set on.
 +
#*IONICUBE 4 axis board rev. 007: insert jumper to JP10 position 1 (see image [[IONI & IONICUBE user guide/Making the first Granity connection|here]]),
 +
#*IONICUBE 4 axis board rev. 009 and higher: set the switch S1 position 1 to ON (see image [[IONI & IONICUBE user guide/Making the first Granity connection|here]]), and
 +
#*IONICUBE 1X, set DIP switch S1 position 1 on).
 +
# Power up the 24 VDC power. Some leds should start blinking at the drive.
 +
# Launch Granity software and:
 +
##Go to Connect tab
 +
##Ensure that SM V2 USB adapter is selected from dropdown list called ''Communication interface device''
 
##Click ''Connect to drive''
 
##Click ''Connect to drive''
 
##Once list of connected drives pop up, select the one you connected and click ''Open''
 
##Once list of connected drives pop up, select the one you connected and click ''Open''
  
 
Now if everything has gone well, you should see information like drive model and serial number on the Connect tab. Connection has been successfully tested and drive may be disconnected to proceed with next setup step.
 
Now if everything has gone well, you should see information like drive model and serial number on the Connect tab. Connection has been successfully tested and drive may be disconnected to proceed with next setup step.
 +
 
==Disconnecting==
 
==Disconnecting==
 
To disconnect, just click '''Disconnect from drive''' button. Before disconnecting ensure following:
 
To disconnect, just click '''Disconnect from drive''' button. Before disconnecting ensure following:
Line 78: Line 93:
  
 
==Upgrading drive firmware==
 
==Upgrading drive firmware==
Preparations:
+
See the main article [[Granity user guide/Uploading a firmware]].
#Back-up drive settings to file as firmware upgrade may reset them to factory defaults
+
#Ensure that communicatation works flawlessly to the device (in normal Granity operations)
+
#Ensure that you have the firmware files
+
##Original firmware (available from product site) - this file may be useful to restore device in factory state
+
##A compatible new friwmare file for your device model & version
+
Procedure to upgrade firmware on the device:
+
#[[Setting device bus address|Set device address]] to firmware upgrade state and power up drive
+
#Click '''Connect to drive'''
+
#List of available devices pops up, open the one with firmware upgrade mode active
+
#Firmware upgrade dialog pops up. Click '''Open file & start upgrade''' button
+
#Firmware upgrade starts, wait until it finishes
+
#Close upgrade dialog, power off the drive and restore the [[Setting device bus address|address]] settings to normal
+
  
 
==Troubleshooting==
 
==Troubleshooting==
* Check if [[Argon user guide/LED indicators|Argon LED status indicators]] are indicating an error
+
* Check if LEDs are indicating an error (LEDs of: [[Argon user guide/LED indicators|Argon]], [[IONI & IONICUBE user guide/LED indicators|Ioni]])
* Ensure that each device in the bus has unique [[Setting device bus address|address]] selected
+
* Ensure that each device in the bus has unique selected ([[Setting device bus address|Argon]])
* Ensure correct interface device has been selected
+
* Ensure correct interface device has been selected from the dropdown list. If multiple choices are shown, try the other ones. If adapter is not shown, try restarting Granity.
* Ensure that [[Setting device bus address|bus termination]] setting has been properly set on only on the last drive in the bus
+
* Ensure that bus termination has been properly set on only on the last drive in the bus  
[[Category:Granity user guide]]
+
**[[Setting device bus address|Argon bus termination]]
 +
**For IONICUBE (4 axis) ensure that jumper in JP10 position 3 is inserted
 +
**For IONICUBE 1X, ensure that S1 position 1 is switched on)
 +
*See [[Device connection troubleshooting]]
 +
{{next|[[Granity user guide/Goals]]}}
 +
 
 +
[[Category:Granity_user_guide]]

Latest revision as of 07:59, 27 April 2017

Granityconnect.png

This tab serves following purposes:

  • Connecting and disconnecting to a drive
  • Loading and saving settings
  • Clear drive fault state
  • Enable or disable motor control
  • Restart drive
  • Upgrade firmware of the drive

Connecting[edit | edit source]

Preparations[edit | edit source]

Before connecting drive to Granity, read through Argon setup guide.

Minimum requirements for connection:

Establishing connection[edit | edit source]

Argon[edit | edit source]

  1. Connect PE of J4 connector to protective earth. After that wire 24 VDC power supply to Argon's J3 connector, however do not power up yet.
  2. Set drive address to give an bus address to the device.
  3. Connect Argon J2 (any of two ports) connector to SimpleMotion V2 USB adapter with a straight Ethernet cable and plug USB adapter to computer.
  4. Power up the 24 VDC power. Some leds should start blinking at the drive (specifily LD3 and/or LD4).
  5. Launch Granity software and:
    1. Go to Connect tab
    2. Ensure that SM V2 USB adapter is selected from dropdown list called Communication interface device
    3. Click Connect to drive
    4. Once list of connected drives pop up, select the one you connected and click Open

IONICUBE[edit | edit source]

  1. Wire up IONICUBE logic power (24V) supply.
  2. Connect IONICUBE connector X1 (any of two ports) connector to SimpleMotion V2 USB adapter with a straight Ethernet cable and plug USB adapter to computer.
  3. Make sure that SM bus termination is set on.
    • IONICUBE 4 axis board rev. 007: insert jumper to JP10 position 1 (see image here),
    • IONICUBE 4 axis board rev. 009 and higher: set the switch S1 position 1 to ON (see image here), and
    • IONICUBE 1X, set DIP switch S1 position 1 on).
  4. Power up the 24 VDC power. Some leds should start blinking at the drive.
  5. Launch Granity software and:
    1. Go to Connect tab
    2. Ensure that SM V2 USB adapter is selected from dropdown list called Communication interface device
    3. Click Connect to drive
    4. Once list of connected drives pop up, select the one you connected and click Open

Now if everything has gone well, you should see information like drive model and serial number on the Connect tab. Connection has been successfully tested and drive may be disconnected to proceed with next setup step.

Disconnecting[edit | edit source]

To disconnect, just click Disconnect from drive button. Before disconnecting ensure following:

  • Have you changed some parameters without pressing Apply settings button afterwards?
  • Have you modified settings and wish to keep the changes? If yes, see #Loading and saving settings

Enable or disable motor control[edit | edit source]

Enable/disable feature sets drive in active (enabled) or inactive (disabled) state. In enabled state drive performs motor control (such as positioning) and in disabled states drive lets motor free-wheel (torque off) or brakes motor.

Disabling drive[edit | edit source]

  • To disable drive, click Disable drive button or Esc key from anywhere in the software
  • Alternatively set logic 0 to Enable drive physical input

Enabling drive[edit | edit source]

  • To enable drive, click Enable drive buttton
  • In order to enable drive, logic 1 must be at drive physical Enable drive input

Verifying current enable/disable status[edit | edit source]

Loading and saving settings[edit | edit source]

Different locations and transfer ways of parameters between drive, Granity and file system

Drive parameters have three possible storage medias:

Drive internal parameter memory (RAM)
  • This holds currently active set of parameters in the drive
  • These parameters are automatically fetched to the user interface every time Granity is connected to drive
  • RAM parameters are overridden by the present values of the user interface when Apply settings button is pressed
Drive internal non-volatile memory (Flash)
  • Parameters in this memory will 'stick' in drive when device is powered off
  • These parameters are automatically loaded to RAM during drive power-on
  • To store parameters from RAM to Flash, click Save settings to drive non-volatile memory button
User interface (UI)
  • Parameters visible on Granity user interface
  • Can be modified by user
  • UI parameters can be transferred to drive (Apply) or to file
File on computer filesystem
  • Parameters may be also stored and loaded from a file (file name ending: .drc)
  • To load settings, click Load settings from file and to activate these settings in drive, click Apply settings
  • To save settings currently present in the user interface to file, click Save settings to file

Clearing drive faults[edit | edit source]

If drive enters in fault state, it typically can be cleared by clicking Clear drive faults button or performing equivalent reset errors command via phyiscal IO pins.

Some faults are clearable only by restarting drive. Restarting may be done by clicking Restart drive or by cycling 24VDC power. Restart is needed if Permanent stop status register bit is on. Note: Permanent stop bit is turned on also by changing certain parameters (not a fault).


Upgrading drive firmware[edit | edit source]

See the main article Granity user guide/Uploading a firmware.

Troubleshooting[edit | edit source]

  • Check if LEDs are indicating an error (LEDs of: Argon, Ioni)
  • Ensure that each device in the bus has unique selected (Argon)
  • Ensure correct interface device has been selected from the dropdown list. If multiple choices are shown, try the other ones. If adapter is not shown, try restarting Granity.
  • Ensure that bus termination has been properly set on only on the last drive in the bus
    • Argon bus termination
    • For IONICUBE (4 axis) ensure that jumper in JP10 position 3 is inserted
    • For IONICUBE 1X, ensure that S1 position 1 is switched on)
  • See Device connection troubleshooting