Editing Overvoltage and undervoltage faults

Jump to: navigation, search

Warning: You are not logged in. Your IP address will be publicly visible if you make any edits. If you log in or create an account, your edits will be attributed to your username, along with other benefits.

The edit can be undone. Please check the comparison below to verify that this is what you want to do, and then save the changes below to finish undoing the edit.

This page supports semantic in-text annotations (e.g. "[[Is specified as::World Heritage Site]]") to build structured and queryable content provided by Semantic MediaWiki. For a comprehensive description on how to use annotations or the #ask parser function, please have a look at the getting started, in-text annotation, or inline queries help page.

Latest revision Your text
Line 1: Line 1:
Drive faulting due to voltage fluctuations in [[HV DC bus]] are commonly experienced with servo systems. These faults occur when drive measures a HV DC bus supply voltage that is not within the range defined by {{param|FUV}} and {{param|FOV}} parameters. The deviation of voltage may be impossible to notice with multimeter as length of these voltage surges can be in millisecond range.
+
Drive faulting due to voltage fluctuations in [[HV DC bus]] are commonly experienced with servo systems. These faults occur when drive measures a HV DC bus supply voltage that is not within the range defined by [[FUV]] and [[FOV]] parameters. The deviation of voltage may be impossible to notice with multimeter as length of these voltage surges can be in millisecond range.
  
 
==Overvoltage faults==
 
==Overvoltage faults==
Servo drive attached to a motor can act two ways: energy supply and energy consumer. The energy consumer behavior occurs during decelerations and during fast torque reversals, and this causes current flow from motor to drive power supply capacitors. If the generated energy is not absorbed anywhere, the voltage of HV DC bus capacitors will rise above overvoltage threshold ({{param|FOV}}) and trigger an software cleanable overvoltage fault. Overvoltage faults that are caused by returned energy from motor, can be dealt with a [[regenerative resistor]] and with optional extra capacitance in HV DC bus.  
+
Servo drive attached to a motor can act two ways: energy supply and energy consumer. The energy consumer behavior occurs during decelerations and during fast torque reversals, and this causes current flow from motor to drive power supply capacitors. If the generated energy is not absorbed anywhere, the voltage of HV DC bus capacitors will rise above overvoltage threshold ([[FOV]]) and trigger an software cleanable overvoltage fault. Overvoltage faults that are caused by returned energy from motor, can be dealt with a [[regenerative resistor]] and with optional extra capacitance in HV DC bus.  
  
 
Scenarios where returned energy is causing the rise of HV DC bus voltage:
 
Scenarios where returned energy is causing the rise of HV DC bus voltage:
Line 10: Line 10:
 
<gallery widths="330px" heights="500px">
 
<gallery widths="330px" heights="500px">
 
File:regeneration1.png|Voltage generation during deceleration of motor (motor current is negative, current is pumped to HV DC bus causing a 40 VDC rise). Top: motor torque command, middle: velocity, bottom: HV DC bus voltage.
 
File:regeneration1.png|Voltage generation during deceleration of motor (motor current is negative, current is pumped to HV DC bus causing a 40 VDC rise). Top: motor torque command, middle: velocity, bottom: HV DC bus voltage.
File:regeneration2.png|Voltage generation during deceleration of motor (motor current is negative, current is pumped to HV DC bus). However, in this case drive is equipped with regenerative resistor and tightly set {{param|FOV}} parameter which prevents the significant voltage rise (only 5 VDC rise).
+
File:regeneration2.png|Voltage generation during deceleration of motor (motor current is negative, current is pumped to HV DC bus). However, in this case drive is equipped with regenerative resistor and tightly set [[FOV]] parameter which prevents the significant voltage rise (only 5 VDC rise).
 
File:regeneration3accel.png|Example of accelerating motor (motor current is positive, power is drawn from HV DC bus which is causing a temporary voltage drop). Rectified 50 Hz mains AC ripple is easily seen in the voltage graph.
 
File:regeneration3accel.png|Example of accelerating motor (motor current is positive, power is drawn from HV DC bus which is causing a temporary voltage drop). Rectified 50 Hz mains AC ripple is easily seen in the voltage graph.
 
</gallery>
 
</gallery>
Line 37: Line 37:
  
 
Most suitable type of resistors are the ones that can handle high peak power without damage. These are common wire wound power resistors that can handle typically ~10 times more power in short periods than their actual rating.
 
Most suitable type of resistors are the ones that can handle high peak power without damage. These are common wire wound power resistors that can handle typically ~10 times more power in short periods than their actual rating.
{{tip|If resistor is constantly heating even when machine is not moving, it means that drive's overvoltage fault limit {{param|FOV}} is set too low compared to the [[HV DC bus]] voltage (drive thinks it's burning regenerative energy, but it's really burning supplied power). Try increasing FOV value or reducing supply voltage until heating stops and resistor stays cool when motors are idle.}}
+
{{tip|If resistor is constantly heating even when machine is not moving, it means that drive's overvoltage fault limit [[FOV]] is set too low compared to the [[HV DC bus]] voltage (drive thinks it's burning regenerative energy, but it's really burning supplied power). Try increasing FOV value or reducing supply voltage until heating stops and resistor stays cool when motors are idle.}}
  
 
==Undervoltage faults==
 
==Undervoltage faults==
Line 45: Line 45:
 
===Variables used in equations===
 
===Variables used in equations===
 
*<math>t_{duration}</math> = time duration in seconds which capacitor should be able to help at maximum current surge
 
*<math>t_{duration}</math> = time duration in seconds which capacitor should be able to help at maximum current surge
*<math>L_{MotorInductance}</math> = motor coil inductance in Henrys (use value of {{param|ML}}/1000)
+
*<math>L_{MotorInductance}</math> = motor coil inductance in Henrys (use value of [[ML]]/1000)
*<math>I_{PeakMotorCurrent}</math> = motor peak current in Amps (use value of {{param|MMC}}/1000)
+
*<math>I_{PeakMotorCurrent}</math> = motor peak current in Amps (use value of [[MMC]]/1000)
 
*<math>U_{MaxVoltageChange}</math> = maximum voltage change in HV DC bus during this current surge/peak. I.e. if drive is set to fault at 56V and supply voltage is 48VDC, then 56-48V=8V should be used.
 
*<math>U_{MaxVoltageChange}</math> = maximum voltage change in HV DC bus during this current surge/peak. I.e. if drive is set to fault at 56V and supply voltage is 48VDC, then 56-48V=8V should be used.
 
*<math>scaler</math> = a user chosen value between 0.1 to 1.0. 1.0 is for the worst case where we assume instantaneous torque reversal (rare) and lower values can be used with slower change of torque direction.  
 
*<math>scaler</math> = a user chosen value between 0.1 to 1.0. 1.0 is for the worst case where we assume instantaneous torque reversal (rare) and lower values can be used with slower change of torque direction.  
{{tip|Drive allows voltage few temporarily volts above {{param|FOV}} before faulting. In IONI this voltage is about 4 volts. So when FOV is set to 52V, then drive actually faults at 56V}}
+
{{tip|Drive allows voltage few temporarily volts above [[FOV]] before faulting. In IONI this voltage is about 4 volts. So when FOV is set to 52V, then drive actually faults at 56V}}
 
===Surge duration based method===
 
===Surge duration based method===
 
For short current surges/spikes, a capacitor added to HV DC bus might provide a solution for filtering out the spikes. Capacitor can be sized by equation:
 
For short current surges/spikes, a capacitor added to HV DC bus might provide a solution for filtering out the spikes. Capacitor can be sized by equation:
Line 70: Line 70:
 
= See also =
 
= See also =
 
* [[Configuring drive voltage limits FUV and FOV]]
 
* [[Configuring drive voltage limits FUV and FOV]]
[[Category:Argon_troubleshooting]]
 
[[Category:Argon_user_guide]]
 
[[Category:IONI_troubleshooting]]
 
[[Category:IONI_user_guide]]
 
[[Category:Troubleshooting]]
 