Argon resolver adapters. These plug into Argon J1 port and resolver wires are directly connected to the pads of adapter.

Argon resolver adapter is a small sized device that adds resolver feedback device support to Argon servo drive.

Obtaining adapter

Adapter is available from Granite Devices web shop:

Adapter may be also self-built (schematics: Media:argonresolveradapter_schematics.png)

Usage

Wiring

Connection of resolver to adapter.

Resolver has total of 6 wires and 3 windings: one for rotor (primary) and two stators (secondaries). Rotor connects to the adapter pins A+ and A- while secondaries connect to B+/- and C+/-.

If pin-out of resolver is unknown, it can be found out with multimeter by finding the wire pairs where coils are connected. Rotor can be identified by searching for lowest resistance coil. Stators typically have at least twice as high resistance compared to rotor.

A shielded cable is required and shield should be connected to D-sub connector frame to reduce EMI noise. Shielded cable for motor power leads and connection of cable shield and motor frame to drive PE is strongly recommended if not necessary to reduce noise. After all noise countermeasures, some noise is still expected from resolver read-out due to analog nature of the signals. This noise will appear as position value noise and motor hiss when standing still or rotating slowly.

Finally plug the adapter to Argon J1 port.

Configuration

To configure drive for resolver:

  • Ensure that drive has at least firmware package version 1.3.0
  • Choose Resolver from feedback device parameter Feedback deviceFBD
  • Set feedback device resolution Feedback device resolutionFBR to 2048 PPR (resolver will give same resolution as 2048 PPR / 8192 count encoder). Note: 2048 is not always the correct value, see Multi-turn or multi-speed resolvers chapter.
  • Tune motor normally. If motor is always unstable or locks motor position, try changing direction of feedback by toggling checkbox Invert feedback directionFBI

Multi-turn or multi-speed resolvers

Some resolvers produce more than one electrical cycle per revolution (resolver's pole pair count greater than 1). This means that also Argon sees it to produce larger position counter change per revolution. For multi pole pair resolvers, multiply the Feedback device resolutionFBR of 2048 PPR by the number of pole pairs. For example, enter FBR value 4096 for 2 pole pair resolver and 8192 for 4 pole pair resolver.

If you're unsure of how many pole pairs the resolver has, just attach it to drive and rotate it manually exactly one revolution while inspecting position counter value at Granity's Testing tab. If you see position counter changing approx 8192 counts, then it's single-turn resolver. If you see change of ~16384 or more, then it's multi-turn resolver. To determine correct Feedback device resolutionFBR value, write down the counter change over one revolution, divide it by 4 and round it to nearest value of 2048, 4096, 6144, 8192 or any N*2048.

Example: if you find position counter changes 16760 counts per mechanical revolution, then divide it by 4 to get 4190, then round it to 4096 which is the correct value for FBR.


In no event the Product Information or parts hereof shall be regarded as guarantee of conditions or characteristics. The Product Information or any part thereof may also not be regarded as a warranty of any kind. No liability of any kind shall be assumed by Author with respect to Product Information or any use made by you thereof, nor shall Author indemnify you against or be liable for any third party claims with respect to such information or any use thereof.

As content of this Wiki may be edited by user community, Granite Devices Oy or it's affiliates do not take any responsibility of the contents of this Wiki. Use information at your own risk. However, Granite Devices staff attempts to review all changes made to this Wiki and keep information trustworthy.

Without written consent, Granite Devices' Products or Intellectual Property shall not be used in situations or installations where living beings, material property, or immaterial property could be harmed by the operation, features or failures of Product. Products may only be used in a way where hazards like moving parts, electric shock, laser radiation, or fire can't be realized even if the content of this Wiki would suggest otherwise.