This article describes an easy method to verify CMD port input signal proper functionality on VSD-E/XE drives.

Note: This testing method works only for following inputs:

  • Opto-in 1
  • Opto-in 2
  • Analog in 1 (as digital input)
  • Analog in 2 (as digital input)

Opto-in 3-4 can't be tested this way because these are shared with serial traffic and would interfere with GDtool connection. However, working GDtool connection proves that inputs 3-4 are working because connection wouldn't be possible otherwise.

Setup[edit | edit source]

Connect drive to GDtool and follow the instructions below.

VSDtestInput1.png

  1. Configure "User bit"
  2. Select input to be tested from configuration dialog
  3. Click Ok
  4. Click Set

Then go to Device status tab

VSDtestInput2.png

4. Monitor "User configured input" status bit and see if it changes as you toggle the selected input signal on CMD port. Green means that drive reads input value as logic 1 (or 0 if invert option selected).

Note: this method doesn't verify fast toggling signals. Status page update interval is 1-2 seconds so shorter than 2 second pulses may not change status color.


In no event the Product Information or parts hereof shall be regarded as guarantee of conditions or characteristics. The Product Information or any part thereof may also not be regarded as a warranty of any kind. No liability of any kind shall be assumed by Author with respect to Product Information or any use made by you thereof, nor shall Author indemnify you against or be liable for any third party claims with respect to such information or any use thereof.

As content of this Wiki may be edited by user community, Granite Devices Oy or it's affiliates do not take any responsibility of the contents of this Wiki. Use information at your own risk. However, Granite Devices staff attempts to review all changes made to this Wiki and keep information trustworthy.

Without written consent, Granite Devices' Products or Intellectual Property shall not be used in situations or installations where living beings, material property, or immaterial property could be harmed by the operation, features or failures of Product. Products may only be used in a way where hazards like moving parts, electric shock, laser radiation, or fire can't be realized even if the content of this Wiki would suggest otherwise.