Signal path of motor drive
In Granite Devices drives the torque, velocity and position limits and setpoints are defined as integer numbers. The vales are represented "hardware" scale which are described below.
Contents
Setpoint signal path
Setpoint signal path converts user setpoint to internal setpoint.
Setpoint signal path
Main parts are:
- Input multiplier. Purpose of this is to increase resolution of input setpoint to allow more fine grained velocity & acceleration control in trajectory planner. By default Setpoint multiplierMUL value is 50.
- Setpoint smoothing filter. If enabled, applies low pass filter to signal reducing jitter and roughness of signal but also introduces about some delay. By default the filter has 100% attenuation at 250Hz.
- Trajectory planner. This limits rate of change of setpoint signal based on Velocity limitCVL and Acceleration limitCAL parameters. Output rate maximum rate of change:
- Velocity changes max Acceleration limitCAL nubmer of units per control cycle (control cycle is 400µs in most GD drives)
- Velocity maximum value is limited to Velocity limitCVL
- Input divider. This divides setpoint signal by Setpoint dividerDIV to give desired output scale for internal setpoint. Combination of multiplier and divider can be used change total scaling of setpoint signal.
Setpoint source scales
Different setpoint sources have different range and scale:
Setpoint source | Type | Range | Scale |
---|---|---|---|
Pulse & directon | Incremental | Infinite |
|
Quadrature | Incremental | Infinite |
|
PWM | Absolute | Full input scale equals setpoint range of +/-16384. In loss of PWM signal, setpoint is 0. |
|
Analog | Full input scale equals setpoint range of +/-16384 | ||
Serial (SimpleMotion V2) | Absolute & incremental | Infinite |
It should be noted that trajectory planner operates after multiplier meaning that Velocity limitCVL velocity limit value is not in equal scale with velocity setpoint value.
Internal setpoint
Internal setpoint is a predefined setpoint scale inside the drive. The scale of internal setpoint signals are:
- Position mode: position sensor counter raw value
- Velocity mode: internal goes through Velocity normalized that changes scales depending on setpoint source:
- In PWM & Analog source: Internal setpoint of +/-16384 represents whole speed range covered by Velocity limitCVL parameter. I.e. 10V input to analog input runs motor at 100% speed and -5V at -50% etc.
- In all other sources: number of feedback device counts per one control cycle. Obtained by calculating the difference of position feedback values at every control cycle.
- Torque mode: Torque normalizer scales internal setpoint so that value of +/-16384 represents full torque scale (i.e. internal setpoint value 16384 outputs configured peak current Peak current limitMMC and 8192 outputs Peak current limitMMC/2)
Controller
The default controller type of GD drives is cascaded type where each controlled variable has it's own PI or P controller. In position mode such structure is called as PIV controller.
The block diagram below represents simplified structure of GD drives.
Setpoint scale examples
Assuming control cycle to be 400µs / 2500 Hz (default in GD drives).
Example 1
- Calculating setpoint in velocity mode
- Motor has 2500 P/R encoder (10000 CPR) and user wants to rotate it at 1000 rpm in velocity mode. Scaling is set to 1:1 (MUL/DIV ratio is 1)
- Rotation speed is 1000/60 = 16.667 revs/s (RPS) Needed encoder count frequency is 16.667*10000 = 16667 counts/s.
- Internal setpoint is the amount of counts per control cycle so in this case it's 16667/2500 = 66.667
Because set point is integer value user must round setpoint to 66 or 67. To achieve exact speed, he could change input scaling (MUL/DIV) to allow unrounded value here.
- Calculating acceleration and velocity limit parameters
If DIV is 50, then user must have Velocity limitCVL value at least 3333 (66.6667*50).
If user wants motor to accelerate to 1000 rpm in 0.1 seconds, then Acceleration limitCAL is value should be 3333/2500/0.1 = 13.33. Value must be again rounded to integer and rounding error could be reduced by adjusting scaling (adjust DIV).
Granity calculates real world units thus it can be used to calculate and experiment with the scales. As scales are linear, interpolation of values is viable choice. |
See also
In no event the Product Information or parts hereof shall be regarded as guarantee of conditions or characteristics. The Product Information or any part thereof may also not be regarded as a warranty of any kind. No liability of any kind shall be assumed by Author with respect to Product Information or any use made by you thereof, nor shall Author indemnify you against or be liable for any third party claims with respect to such information or any use thereof.
As content of this Wiki may be edited by user community, Granite Devices Oy or it's affiliates do not take any responsibility of the contents of this Wiki. Use information at your own risk. However, Granite Devices staff attempts to review all changes made to this Wiki and keep information trustworthy.
Without written consent, Granite Devices' Products or Intellectual Property shall not be used in situations or installations where living beings, material property, or immaterial property could be harmed by the operation, features or failures of Product. Products may only be used in a way where hazards like moving parts, electric shock, laser radiation, or fire can't be realized even if the content of this Wiki would suggest otherwise.