This page supports semantic in-text annotations (e.g. "[[Is specified as::World Heritage Site]]") to build structured and queryable content provided by Semantic MediaWiki. For a comprehensive description on how to use annotations or the #ask parser function, please have a look at the getting started, in-text annotation, or inline queries help page.

Latest revision Your text
Line 1: Line 1:
[[File:Argonresolveradapter.jpg|thumb|320px|Argon resolver adapters. These plug into Argon J1 port and resolver wires are directly connected to the pads of adapter.]]
+
Argon resolver adapter is a small sized adapter device that adds [[Feedback devices|resolver]] feedback device support to [[Argon]] servo drive.
Argon resolver adapter is a small sized device that adds [[Feedback devices|resolver]] feedback device support to [[Argon]] servo drive.
+
==Obtaining adapter==
+
Adapter is available from [[Granite Devices web shop]]:
+
*[http://shop.granitedevices.com/product/38/argon-resolver-adapter Argon resolver adapter on Web shop]
+
Adapter may be also self-built (schematics: [[Media:argonresolveradapter_schematics.png]])
+
==Usage==
+
===Wiring===
+
[[File:Resolveradapterwiring.png|thumb|320px|Connection of resolver to adapter.]]
+
Resolver has total of 6 wires and 3 windings: one for rotor (primary) and two stators (secondaries). Rotor connects to the adapter pins A+ and A- while secondaries connect to B+/- and C+/-.
+
 
+
If pin-out of resolver is unknown, it can be found out with multimeter by finding the wire pairs where coils are connected. Rotor can be identified by searching for lowest resistance coil. Stators typically have at least twice as high resistance compared to rotor.
+
 
+
A shielded cable is required and shield should be connected to D-sub connector frame to reduce [[EMI]] noise. Shielded cable for motor power leads and connection of cable shield and motor frame to drive PE is strongly recommended if not necessary to reduce noise. After all noise countermeasures, some noise is still expected from resolver read-out due to analog nature of the signals. This noise will appear as position value noise and motor hiss when standing still or rotating slowly.
+
 
+
Finally plug the adapter to Argon J1 port.
+
 
+
===Configuration===
+
To configure drive for resolver:
+
*Ensure that drive has at least [[Argon firmware releases|firmware]] package version 1.3.0
+
*Choose Resolver from feedback device parameter {{param|FBD}}
+
*Set feedback device resolution {{param|FBR}} to 2048 PPR (resolver will give same resolution as 2048 PPR / 8192 count encoder). Note: 2048 is not always the correct value, see ''Multi-turn or multi-speed resolvers'' chapter.
+
*Tune motor normally. If motor is always unstable or locks motor position, try changing direction of feedback by toggling checkbox {{param|FBI}}
+
====Multi-turn or multi-speed resolvers====
+
Some resolvers produce more than one electrical cycle per revolution (resolver's pole pair count greater than 1). This means that also Argon sees it to produce larger position counter change per revolution. For multi pole pair resolvers, multiply the {{param|FBR}} of 2048 PPR by the number of pole pairs. For example, enter FBR value 4096 for 2 pole pair resolver and 8192 for 4 pole pair resolver.
+
 
+
If you're unsure of how many pole pairs the resolver has, just attach it to drive and rotate it manually exactly one revolution while inspecting position counter value at Granity's Testing tab. If you see position counter changing approx 8192 counts, then it's single-turn resolver. If you see change of ~16384 or more, then it's multi-turn resolver. To determine correct {{param|FBR}} value, write down the counter change over one revolution, divide it by 4 and round it to nearest value of 2048, 4096, 6144, 8192 or any N*2048.
+
 
+
Example: if you find position counter changes 16760 counts per mechanical revolution, then divide it by 4 to get 4190, then round it to 4096 which is the correct value for FBR.
+
 
+
[[Category:Hardware]]
+
[[Category:Argon]]
+

Please note that all contributions to Granite Devices Knowledge Wiki may be edited, altered, or removed by other contributors. If you do not want your writing to be edited mercilessly, then do not submit it here.
You are also promising us that you wrote this yourself, or copied it from a public domain or similar free resource (see Granite Devices Knowledge Wiki:Copyrights for details). Do not submit copyrighted work without permission!

Select categories:

To edit this page, please answer the question that appears below (more info):

Cancel | Editing help (opens in new window)

Template used on this page: