If there's problem getting rid of permanent under voltage fault in Argon, it may be caused by following reasons:

  • STO1 input is not powered by 24 VDC
  • Drive's internal fuse has blown. To check this safely discharge drive, remove cover, remove fuse and measure fuse resistance. If high current & power is demanded from the drive, then a higher amperage fuse may be installed in the place of original. Maximum fuse size is 16A slow blow and the factory default is between 6.3-8 A slow blow.

Drive internal AC circuity

Argon ac input.png