Difference between revisions of "Argon user guide/Power supply safe discharging"

From Granite Devices Knowledge Wiki
Jump to: navigation, search
[checked revision][checked revision]
 
(6 intermediate revisions by the same user not shown)
Line 4: Line 4:
  
 
To safely discharge Argon voltages:  
 
To safely discharge Argon voltages:  
# Remove AC power (both L and N lines). This can be done for example by unplugging the power cord from wall socket where the power comes from.
+
# Remove power from J4 connector (both L and N lines). This can be done for example by unplugging the power cord from wall socket where the power comes from.
# Wait 3 to 5 minutes after removing AC to allow capacitor voltage discharge.
+
# Wait at least 3 minutes after de-energization to allow capacitor voltage discharge.
# Measure a DC voltage between VN and VP terminals of J4 connector with a multimeter rated up to 600 VDC. Voltage has discharged if VN-VP voltage is less than 20 VDC.
+
# Measure a DC voltage between VN and VP terminals of J4 connector with a multimeter rated at least up to 600 VDC as the worst case drive internal HV voltage may be over 400 VDC. '''Voltage has been successfully discharged if VN-VP voltage is less than 5 VDC.'''
 
{{electricshock|If DC voltage between VN and VP terminals of J4 connector is above 20 VDC after 3 minutes of de-energization, drive has internal failure of discharging circuity. In such case danger may be present even after weeks of wait. Contact your supplier first for further assistance before continuing servicing.}}
 
{{electricshock|If DC voltage between VN and VP terminals of J4 connector is above 20 VDC after 3 minutes of de-energization, drive has internal failure of discharging circuity. In such case danger may be present even after weeks of wait. Contact your supplier first for further assistance before continuing servicing.}}
  
 
Discharging 24 VDC supply does happen instantly after 24 V has been removed. However, this does not affect AC side discharge in any way.
 
Discharging 24 VDC supply does happen instantly after 24 V has been removed. However, this does not affect AC side discharge in any way.
[[Category:Setup guides]]
+
 
[[Category:Argon]]
+
[[Category:Argon_user_guide]]

Latest revision as of 13:17, 7 April 2016

Power supplies and drives have capacitors that store electricity even when power supply has been disconnected from the power network. This poses electric shock hazard when touching a device, or its wiring, that has been recently unplugged from the power line.

Safely discharging Argon drive[edit | edit source]

Argon (servo drive) has internal power supply bleeding resistor that will discharge the capacitors during 5 minutes after AC power has been removed.

To safely discharge Argon voltages:

  1. Remove power from J4 connector (both L and N lines). This can be done for example by unplugging the power cord from wall socket where the power comes from.
  2. Wait at least 3 minutes after de-energization to allow capacitor voltage discharge.
  3. Measure a DC voltage between VN and VP terminals of J4 connector with a multimeter rated at least up to 600 VDC as the worst case drive internal HV voltage may be over 400 VDC. Voltage has been successfully discharged if VN-VP voltage is less than 5 VDC.

Discharging 24 VDC supply does happen instantly after 24 V has been removed. However, this does not affect AC side discharge in any way.