Difference between revisions of "Fault location"

From Granite Devices Knowledge Wiki
Jump to: navigation, search
[checked revision][checked revision]
(List of Fault location ID 1)
Line 7: Line 7:
 
! Fault location ID 1 !! Reason !! Solution
 
! Fault location ID 1 !! Reason !! Solution
 
|-
 
|-
| 120 || Short circuit protection triggered || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]].
+
| 120 || Short circuit protection triggered (very high current rise detected) || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]].
 
|-
 
|-
 
| 600 || Overcurrent protection (slower reaction but lower current level than short circuit protection) triggered || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]].
 
| 600 || Overcurrent protection (slower reaction but lower current level than short circuit protection) triggered || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]].
Line 13: Line 13:
 
| 5500 || Motor type [[MT]] not selected || Choose [[MT]]
 
| 5500 || Motor type [[MT]] not selected || Choose [[MT]]
 
|}
 
|}
 +
 
==List of Fault location ID 2==
 
==List of Fault location ID 2==
 
The list is incomplete.
 
The list is incomplete.
  
 
[[category:Granity user guide]]
 
[[category:Granity user guide]]

Revision as of 21:52, 16 September 2013

Fault location ID 1 & 2 that are displayed on Granity Testing tab Device state section. Fault locations are detailed numeric codes giving a hint what was the precise reason causing a fault state.

List of Fault location ID 1

The list is incomplete.

Fault location ID 1 Reason Solution
120 Short circuit protection triggered (very high current rise detected) Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform Tuning position controller, adjust FOC.
600 Overcurrent protection (slower reaction but lower current level than short circuit protection) triggered Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform Tuning position controller, adjust FOC.
5500 Motor type MT not selected Choose MT

List of Fault location ID 2

The list is incomplete.