Set this as low as possible without getting OC faults in normal use to maximally protect your equipment. If larger than ''Medium'' setting is needed, see [[Over current fault troubleshooting]] for solution to the problem.
 
Set this as low as possible without getting OC faults in normal use to maximally protect your equipment. If larger than ''Medium'' setting is needed, see [[Over current fault troubleshooting]] for solution to the problem.
 
|-
 
|-
| FOV || Over voltage fault threshold || Maximum allowed HV DC bus voltage before entering into over voltage fault. Also defines at which voltage drive starts driving [[Argon user guide/Braking resistor|braking resistor]] to reduce bus voltage.  Set FOV value at least 10% higher than nominal HV DC bus voltage (FOV=1.55*AC voltage in AC powered drives, such as [[Argon]]).|| Suggested value at different mains AC voltages for AC powered drives:
+
| FOV || Over voltage fault threshold || Maximum allowed HV DC bus voltage before entering into over voltage fault. Also defines at which voltage drive starts driving [[Argon user guide/Braking resistor|braking resistor]] to reduce bus voltage.|| See [[Configuring drive voltage limits FUV and FOV]].
*220-240 VAC mains, set this 355-380 VDC
+
*110-120 VAC mains, set this to 170-200 VDC
+
 
+
See also [[Overvoltage and undervoltage faults]]
+
 
|-
 
|-
| FUV || Under voltage fault threshold || Minimum allowed HV DC bus voltage before drive starts motor initialization after power-on. Also if this voltage is exceeded during active operation, drive enters into under voltage fault state. || Suggested value at different mains AC voltages for AC powered drives:
+
| FUV || Under voltage fault threshold || Minimum allowed HV DC bus voltage before drive starts motor initialization after power-on. Also if this voltage is exceeded during active operation, drive enters into under voltage fault state. || See [[Configuring drive voltage limits FUV and FOV]].
*220-240 VAC mains, set this 200 VDC
+
*110-120 VAC mains, set this to 100 VDC
+
 
+
See also [[Overvoltage and undervoltage faults]]
+
 
|}
 
|}
  
Line 33: Line 25:
 
| FFT || Goal fault filter time  || Set time filter for this fault group. Defines how long drive allows exceeding these conditions before entering into fault state. || Normally values between 0-0.5 seconds are safe. Higher value may pose danger to user or equipment as motor is not being stopped soon after error condition.
 
| FFT || Goal fault filter time  || Set time filter for this fault group. Defines how long drive allows exceeding these conditions before entering into fault state. || Normally values between 0-0.5 seconds are safe. Higher value may pose danger to user or equipment as motor is not being stopped soon after error condition.
 
|-
 
|-
| FPT || Position tracking error threshold || Defines how much position may deviate from the setpoint || rowspan=3|The value is set as hardware units. Adjust the value and observe the right side value displaying the hardware value converted to a real world units such as ''revolutions/s''. Make sure [[Granity user guide/Machine|Machine tab]] settings are set-up first to get correct conversion.  
+
| FPT || Position tracking error threshold || Defines how much position may deviate from the setpoint || rowspan="3" |The value is set as hardware units. Adjust the value and observe the right side value displaying the hardware value converted to a real world units such as ''revolutions/s''. Make sure [[Granity user guide/Machine|Machine tab]] settings are set-up first to get correct conversion.  
 
|-
 
|-
 
| FVT|| Velocity tracking error threshold ||Defines how much velocity is allowed to deviate from velocity setpoint
 
| FVT|| Velocity tracking error threshold ||Defines how much velocity is allowed to deviate from velocity setpoint

Revision as of 21:00, 21 September 2016

GranityFaultlimits.png

This tab serves as:

  • Set fault triggering levels and tolerances

Parameters

Drive fault limits

Short GUI name GUI name Description How to use
FOC Over current tolerance Set sensitivity of over current faults This variable defines how much over current (measured motor phase current above the peak current limit (Machine/MMC) drive allows before entering into fault state. The Minimum setting has lowest threshold and gives fault easier, Maximum tolerates largest over current spikes before faulting.

Set this as low as possible without getting OC faults in normal use to maximally protect your equipment. If larger than Medium setting is needed, see Over current fault troubleshooting for solution to the problem.

FOV Over voltage fault threshold Maximum allowed HV DC bus voltage before entering into over voltage fault. Also defines at which voltage drive starts driving braking resistor to reduce bus voltage. See Configuring drive voltage limits FUV and FOV.
FUV Under voltage fault threshold Minimum allowed HV DC bus voltage before drive starts motor initialization after power-on. Also if this voltage is exceeded during active operation, drive enters into under voltage fault state. See Configuring drive voltage limits FUV and FOV.

Goal deviation faults

These settings define how much motor may deviate from the setpoints or allowed operating conditions before entering in fault state.

Short GUI name GUI name Description How to use
FFT Goal fault filter time Set time filter for this fault group. Defines how long drive allows exceeding these conditions before entering into fault state. Normally values between 0-0.5 seconds are safe. Higher value may pose danger to user or equipment as motor is not being stopped soon after error condition.
FPT Position tracking error threshold Defines how much position may deviate from the setpoint The value is set as hardware units. Adjust the value and observe the right side value displaying the hardware value converted to a real world units such as revolutions/s. Make sure Machine tab settings are set-up first to get correct conversion.
FVT Velocity tracking error threshold Defines how much velocity is allowed to deviate from velocity setpoint
FEV Over speed fault Defines the maximum allowed speed (feedback based) which the axis is allowed to operate before entering to the overspeed fault state
FMO Motion fault threshold Defines the sensitivity to enter into motion fault. Used for detecting mechanically blocked motion and DC motor runaway (loss of feedback) If motion fault feature needed, adjust the value experimentally by increasing it until faults don't occur in normal use. A good starting value may be motor continuous current in milliamperes/2.
LSF Limit switch function Define drive action when position is out of allowed travel range (i.e. limit switch input is open). Device specific notes:
  • Argon: the Servo stop option is not implemented
  • Other drives (i.e. IONI and ATOMI): LSF also works with software limits (when Position soft high limitHHL and Position soft low limitHLL are set and homing is successfully finished
Choose preferred action when position of motor is beyond allowed travel (i.e. physical limit switches are open). Choices:
  • Do nothing: no action is taken beyond travel limits (in other words, drive ignores travel limit)
  • Disable torque: drive will set internal torque setpoint to zero if torque direction is set to cause motor go further from allowed travel direction (in other words, torque is allowed only towards allowed travel direction)
  • Fault stop: drive sets Motion fault state active which sets drive in inactive state (i.e. motor will be braked and requires user action to move motor back to allowed travel range and then clear fault state)
  • Servo stop: drive attempts to actively brake motor if it's being commanded to out of travel bounds but allows command towards allowed direction