Difference between revisions of "Argon user guide/Braking resistor"
[checked revision] | [checked revision] |
Line 15: | Line 15: | ||
Example of suitable resistor: Tyco HSC 250 82R. [http://passives.te.com/pdf/TycoPowerComponentsShortform.pdf Data sheet] | Example of suitable resistor: Tyco HSC 250 82R. [http://passives.te.com/pdf/TycoPowerComponentsShortform.pdf Data sheet] | ||
==Installation== | ==Installation== | ||
− | [File:Brakingreswiring.png|thumb|500px|Wiring of braking resistor to Argon drive] | + | [[File:Brakingreswiring.png|thumb|500px|Wiring of braking resistor to Argon drive]] |
The image above shows proper wiring of braking resistor. Proper installation has: | The image above shows proper wiring of braking resistor. Proper installation has: | ||
* Shielded cable with 3 conductors with wire gauge at least 0.75 mm² / 18 AWG | * Shielded cable with 3 conductors with wire gauge at least 0.75 mm² / 18 AWG |
Revision as of 17:15, 17 December 2012
Regenerative resistors are usually a required part with servo drives to absorb returned energy from decelerating or braking servo axis.
Servo drive with motor can act two ways: energy supply and energy generator. The generator behavior occurs during decelerations and this causes current flow from motor to drive power supply capacitors. If that generated energy is not absorbed anywhere, the voltage of capacitors will rise above overvoltage threshold and trigger an software clearable overvoltage fault.
Argon supports connecting braking resistor directly to drive J4 connector.
Suitable resistor type
Recommended resistor specifications:
- Resistance 80-100 ohms
- Power rating 150-300 Watts
- Wire wound construction (no film resistors)
- Preferrable in metal housing for grounding/noise shielding
The 250W resistor in the image can absorb enough peak energy to stop 100 kg mechanical linear axis moving up to 3 m/s.
Example of suitable resistor: Tyco HSC 250 82R. Data sheet
Installation
The image above shows proper wiring of braking resistor. Proper installation has:
- Shielded cable with 3 conductors with wire gauge at least 0.75 mm² / 18 AWG
- Cable shield AND earth conductor connected to drive PE terminal
- Earth conductor connected to resistor casing. Place toothed locking washers between wire terminal and resistor to break the insulating coating of resistor case.
- Two other conductors connected to resistor terminals through 8A fast blow fuse
- Resistor should be also mounted on heat sink
- Additionally it is a recommended to shield the resistor terminals from accidental touching
DANGER the terminals of the resistors are connected to dangerous voltages. Never touch them before drive power has been safely discharged.