Difference between revisions of "Fault location"
From Granite Devices Knowledge Wiki
[checked revision] | [checked revision] |
(→List of Fault location ID 1) |
|||
Line 7: | Line 7: | ||
! Fault location ID 1 !! Reason !! Solution | ! Fault location ID 1 !! Reason !! Solution | ||
|- | |- | ||
− | | 120 || Short circuit protection triggered || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]]. | + | | 120 || Short circuit protection triggered (very high current rise detected) || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]]. |
|- | |- | ||
| 600 || Overcurrent protection (slower reaction but lower current level than short circuit protection) triggered || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]]. | | 600 || Overcurrent protection (slower reaction but lower current level than short circuit protection) triggered || Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform [[Tuning position controller]], adjust [[FOC]]. | ||
Line 13: | Line 13: | ||
| 5500 || Motor type [[MT]] not selected || Choose [[MT]] | | 5500 || Motor type [[MT]] not selected || Choose [[MT]] | ||
|} | |} | ||
+ | |||
==List of Fault location ID 2== | ==List of Fault location ID 2== | ||
The list is incomplete. | The list is incomplete. | ||
[[category:Granity user guide]] | [[category:Granity user guide]] |
Revision as of 21:52, 16 September 2013
Fault location ID 1 & 2 that are displayed on Granity Testing tab Device state section. Fault locations are detailed numeric codes giving a hint what was the precise reason causing a fault state.
List of Fault location ID 1
The list is incomplete.
Fault location ID 1 | Reason | Solution |
---|---|---|
120 | Short circuit protection triggered (very high current rise detected) | Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform Tuning position controller, adjust FOC. |
600 | Overcurrent protection (slower reaction but lower current level than short circuit protection) triggered | Check wiring for shorts, ensure that motor inductance is sufficient (especially ironless & pancake motors), perform Tuning position controller, adjust FOC. |
5500 | Motor type MT not selected | Choose MT |
List of Fault location ID 2
The list is incomplete.