Difference between revisions of "Analog setpoint"

From Granite Devices Knowledge Wiki
Jump to: navigation, search
[checked revision][checked revision]
Line 21: Line 21:
  
 
Peak torque can be configured to drive with [[GDtool]] as peak current limit. Torque and current are directly proportional, so torque reference is also a current reference.
 
Peak torque can be configured to drive with [[GDtool]] as peak current limit. Torque and current are directly proportional, so torque reference is also a current reference.
[[Category:Signal]]
+
[[Category:Signals]]

Revision as of 11:16, 18 April 2012

Analog reference is one of reference signal types used in motion control.

The most typical reference voltage range is +/-10V where

  • -10V equals the most negative reference (-100%)
  • 0V equals zero reference
  • 10V equals most positive reference (+100%)
  • Any value between is interpolated linearly

Another common voltage range is 0..5V where zero reference may be at 2.5 VDC (bias voltage).

Differential signaling

Analog reference input in target device is typically differential. Differential input requires 3 wires from source device:

  • Positive input
  • Negative input
  • Ground

The actual reference value will be calculated from the differential of positive and negative inputs. This eliminates error from ground currents and also reduces sensitivity to EMI noise.

Differential signaling on wikipedia

Example

Lets assume +/-10V is used as torque reference in VSD drive. In this case 0V equals no torque, and 10V equals 100% of peak torque configured in the drive, 5V equals 50% torque etc.

Peak torque can be configured to drive with GDtool as peak current limit. Torque and current are directly proportional, so torque reference is also a current reference.