This page supports semantic in-text annotations (e.g. "[[Is specified as::World Heritage Site]]") to build structured and queryable content provided by Semantic MediaWiki. For a comprehensive description on how to use annotations or the #ask parser function, please have a look at the getting started, in-text annotation, or inline queries help page.

Latest revision Your text
Line 3: Line 3:
 
===Wire preparation===
 
===Wire preparation===
 
KANZ motors come with pre-assembled cables for Argon servo drive (encoder and motor part). However, some motor models include excessive 4-pin terminal for motor part that needs to be stripped away.
 
KANZ motors come with pre-assembled cables for Argon servo drive (encoder and motor part). However, some motor models include excessive 4-pin terminal for motor part that needs to be stripped away.
<gallery widths="240px" heights="240px">
+
<gallery widths="200px" heights="200px">
 
File:Kanz termination.jpg|The excessive 4-pin connector that need to be cut away. Stripping 3-5 cm of black outer insulation is recommended to make space for [[EMI suppression cores]].
 
File:Kanz termination.jpg|The excessive 4-pin connector that need to be cut away. Stripping 3-5 cm of black outer insulation is recommended to make space for [[EMI suppression cores]].
 
File:Kanz termination2.jpg|Strip wire ends. Cutting U,V,W 1-2 cm shorter than PE is recommended for safety (to make PE the last to disconnect if cable pulled by force).
 
File:Kanz termination2.jpg|Strip wire ends. Cutting U,V,W 1-2 cm shorter than PE is recommended for safety (to make PE the last to disconnect if cable pulled by force).
Line 29: Line 29:
  
 
{{tip|Pre-made motor configuration files may have significantly different motor resistance {{param|MR}} and inductance {{param|ML}} values compared to motor data sheet. Pre-made files are hand-optimized to give better performance than entering values from data sheet, so it is recommended to leave these values untouched.}}
 
{{tip|Pre-made motor configuration files may have significantly different motor resistance {{param|MR}} and inductance {{param|ML}} values compared to motor data sheet. Pre-made files are hand-optimized to give better performance than entering values from data sheet, so it is recommended to leave these values untouched.}}
 
[[category:Argon user guide]]
 