This page supports semantic in-text annotations (e.g. "[[Is specified as::World Heritage Site]]") to build structured and queryable content provided by Semantic MediaWiki. For a comprehensive description on how to use annotations or the #ask parser function, please have a look at the getting started, in-text annotation, or inline queries help page.

Latest revision Your text
Line 1: Line 1:
This article helps finding cure for connection problems between PC and SimpleMotion based drive (ARGON, IONI, ATOMI etc).
+
This article helps finding cure for connection problems between PC and drive.
===Requirements for connection===
+
==Granity==
[[Granity]] requires following conditions to establish connection:
+
Granity requires following to establish connection:
*Compatible RS485 adapter, such as [[SimpleMotion V2 USB adapter]]
+
*Compatible RS485 adapter, such as [[SimpleMotion V2 USB Adapter]]
*SimpleMotion V2 compliant drive, such as Argon or Ioni
+
*SimpleMotion V2 compliant drive, such as Argon
*SimpleMotion V2 cabling [[SimpleMotion V2 port|with termination]]
+
*SimpleMotion V2 calbing with termination
 
*Correct bus address setting on all devices in the SM V2 bus, see [[Setting device bus address]]
 
*Correct bus address setting on all devices in the SM V2 bus, see [[Setting device bus address]]
*Straight (not crossover) RJ45 cable on the devices with RJ45 ports ([[IONICUBE]], [[ARGON]])
+
===Typical errors===
 
+
*Bus address conflicting between devices (two or more devices set to same address)
=== Common failure reasons ===
+
*Missing bus termination
*Bus [[Setting device bus address|address]] conflicting between devices (two or more devices set to same address)
+
*Device has an error state, see led indicators
*Missing [[Setting device bus address#Bus termination|bus termination]] or too long stub after termination. Correct termination is important especially if RJ45 cable is longer than 3 meters or stub longer than 0.5 meters.
+
**With IONICUBE, make sure that bus termination is set on
+
***IONICUBE 4 axis board rev. 007: insert jumper to JP10 position 1, see image [[IONI & IONICUBE user guide/Making the first Granity connection|here]],
+
***IONICUBE 4 axis board rev. 009 and higher: set switch S1 position 1 ON, see image [[IONI & IONICUBE user guide/Making the first Granity connection|here]], and
+
***IONICUBE 1X, set DIP switch S1 position 1 ON.
+
*Use of crossover RJ45 cable. If this has been used, it might have caused damage that might prevent communication even with correct cable.
+
**For repair instructions of Argon, see [[Determining Argon hardware failure]].
+
*Device has an error state, see [[Argon user guide/LED indicators|led indicators]]
+
 
*Wrong communication interface device selected from Granity
 
*Wrong communication interface device selected from Granity
*[[SimpleMotion V2 USB adapter]] damaged, see [[Testing SimpleMotion V2 USB adapter|testing of SMV2 adapter]]
 
*[[Electromagnetic interference]] that is coupled to the communication cables, try separating signal and power cables and use [[EMI suppression cores]] on cables (including SimpleMotion RJ45).
 
*Device has insufficient logic voltage supply causing erroneous operation or rebooting of device
 
*Possibly some incompatibility with the computer, try connection from another computer
 
*USB adapter has bee plugged in ''after'' Granity has been started (and because of that it is not in listed in the communication interface devices).
 
**Ensure that USB device has been inserted before Granity is started.
 
*Multiple communication interface devices are available and the wrong one has been chosen. Multiple SimpleMotion adapters may be listed even when there is only one SimpleMotion adapter plugged in because Granity might assume some other USB serial port to be also SimpleMotion adapter even when it's not.
 
**Try all available SimpleMotion devices and see which one works.<br />[[File:wikimultipleSMdevices.png]]
 
 
[[Category:Argon_troubleshooting]]
 
[[Category:IONI_troubleshooting]]
 