Difference between revisions of "Tuning torque controller"

From Granite Devices Knowledge Wiki
Jump to: navigation, search
[checked revision][checked revision]
(Manual tuning method)
(Manual tuning method)
Line 8: Line 8:
 
==Manual tuning method==
 
==Manual tuning method==
 
Manual tuning of torque controller is some times done in order to optimize the torque controller response or to find the correct motor resistance [[MR]] and inductance [[ML]] parameters if unknown. Manual tuning also usually yields better torque response than the direct method which may help tuning of velocity or position tuning.
 
Manual tuning of torque controller is some times done in order to optimize the torque controller response or to find the correct motor resistance [[MR]] and inductance [[ML]] parameters if unknown. Manual tuning also usually yields better torque response than the direct method which may help tuning of velocity or position tuning.
{{tip|If satisfactory performance is achieved by direct torque/resistance setting method, you may skip the manual tuning method.}}
+
{{tip|If satisfactory performance was achieved by direct torque & resistance setting method, you may skip the manual tuning method.}}
 
In order to change torque tuning, one needs to change motor resistance [[MR]] and inductance [[ML]] parameters until the torque response looks satisfactory.
 
In order to change torque tuning, one needs to change motor resistance [[MR]] and inductance [[ML]] parameters until the torque response looks satisfactory.
 
===Preparations===
 
===Preparations===

Revision as of 22:28, 26 August 2013

Torque controller tuning means finding the correct gain values for a torque controller inside the servo drive to achieve a proper response from a torque setpoint change.

Direct inductance & resistance method

In Granity, there is no dedicated torque control PI gains as the software supports entering motor coil inductance and resistance where the suitable PI gains are calculated from.

If your motor comes with coil specifications containing phase-to-phase inductance and resistance values, then the only necessary step is to enter the given values into motor resistance MR and inductance ML parameter fields. In case of troubles with this method, proceed with manual tuning method.

Manual tuning method

Manual tuning of torque controller is some times done in order to optimize the torque controller response or to find the correct motor resistance MR and inductance ML parameters if unknown. Manual tuning also usually yields better torque response than the direct method which may help tuning of velocity or position tuning.

In order to change torque tuning, one needs to change motor resistance MR and inductance ML parameters until the torque response looks satisfactory.

Preparations

Correct torque tuning settings on the Testing tab.

Steps to do to begin torque tuning:

  • Ensure that motor is parameterized correctly and working
  • Fix the motor shaft so that it cannot rotate under full peak torque of the motor
  • Make following parameter changes to Granity and click apply afterwards:
    • Set drive in torque control mode CM
    • Set torque bandwidth limit TBW to maximum
    • Choose Serial only setpoint input CM
    • Untick Setpoint smoothing CIS
    • Set Goals tab DIV and MUL to 50
    • Make other necessary adjustments to have drive powered and enabled
  • Set-up the test stimulus and capture settings from Testing tab:
    • Set target setpoint 1 TSP1 to 5000-15000
    • Set delay 1 TSD1 to 0.05 seconds
    • Set target setpoint 2 TSP2 to 0
    • Set delay1 STD2 to 0.5 s
    • Choose sample rate TSR of 10000 Hz or more
    • Choose Capture setpoint change ind positive direction from the dropdown
    • Tick Continuously repeating capture
    • Tick Torque setpoint and Torque achieved from signals
    • Tick Start capture to begin continous capture.
    • Tick Enable test stimulus TSE to begin a pulsed torque generation

Once the steps above are done, motor should be generating short torque pulses to a fixed shaft and torque response graphs should appear on the right side of Granity about once in 3-5 seconds.

Adjusting MR and ML to for optimum torque control

The task here is to adjust the MR and ML parameters to achieve near optimum step response for the torque controller. Observe the images below for guidance.

If the drive faults during this testing due to overcurrent, try reducing TSP1 value or increase fault current tolerance FOC parameter, click Apply, and clear drive faults via the Connect tab.

TorqlowR.png

In this case the resistance MR value has been set too low causing slowly rising achieved torque curve. Such slow response would reduce servo responsiveness.

TorqhighR.png

In the opposite case (too high MR value) the response shows wavy oscillations and ovesrhoot.

TorqlowL.png

Same kind of phenomenon will be seen if motor inductance ML value is too low. Finding oscillation free tuning is finding the correct balance between the MR and ML as both affect each other.

TorqhigL.png

Too high inductance ML will cause sharp overshooting and high frequency oscillations. Motor may produce audible noise if oscillations are continuous (occurs with way too high ML).

Torqgood.png

The above image shows near optimum torque response with fast rising edge combined to minimal overshoot.

Torqgoodspinning.png

The above image shows what may happen if motor shaft is not fixed properly (allowed to rotate). This is withe the optimum settings like the previous image.

Steps to do after manual tuning finished

  • Stop test stimulus by unticking TSE
  • Stop scope catpure by unticking Continuously repeating capture
  • Undo all temporary changes made to settings (such as TBW, CM, DIV, MUL) but leave the optimized MR and ML values active
  • Save settings to drive memory by clicking Save settings on drive non-volatile memory button