SimuCUBE troubleshooting
Over voltage fault
Even with features to reduce the risk, there is a chance that the regenerative resistor circuitry get's damaged. To prevent this, use the latest firmware, and double check your FOV (over voltage fault) setting in Granity.
To check if the regenerative circuitry is damaged, a multimeter (resistance meter) is needed.
- Measure the resistance from the X2 pad HV+ to RES. The measured resistance should be close to 2.2 Ohm in single resistor SimuCUBE boards, and close to 2.35 Ohm in boards where two resistors are soldered.
- Measure the resistance from the X2 pad RES to GND. The measured resistance should be around 12..15 kOhm, changing (lowering) slowly.
Please note, that some multimeters do not compensate for the test wire resistance, and this might lead to higher value when measuring the resistor.
Should the resistor measure more than 5 Ohm, and/or the MOSFET measures less than 10 kOhm, then double check your measurement, and if the results persist, then the respective component need to be changed.
SimuCUBE won't go into DFU mode
- If device does not appear as DFU mode device when plugged in, check Windows Device Manager if there is any unknown USB devices. If yes, then try unplugging SimuCUBE USB cable and see if that device disappears. If this is the case, then it indicates that device driver is not installed properly. Try installing ST DfuSeDemo software with drivers to solve the issue. DfuSeDemo Installation Directory will contain the required drivers.
- Maybe USB device is not recognized at all? Keep Device Manager open and plug/unplug SimuCUBE while keeping eye on the Device Manager list. If you see list refresh, then it is a sign that device has entered/left the list. If nothing happens, then it might indicate hardware issue as no USB device is recognized at all.
- Download & use USBDeview to see whether STM32 BOOTLOADER device or any device missing driver is listed:
SimuCUBE unexpectedly stuck in DFU mode
It is possible, but very rare, that SimuCUBE gets stuck in DFU mode or switches to DFU mode by itself without user interaction. Please refer to separate support article: SimuCUBE stuck in DFU mode
In no event the Product Information or parts hereof shall be regarded as guarantee of conditions or characteristics. The Product Information or any part thereof may also not be regarded as a warranty of any kind. No liability of any kind shall be assumed by Author with respect to Product Information or any use made by you thereof, nor shall Author indemnify you against or be liable for any third party claims with respect to such information or any use thereof.
As content of this Wiki may be edited by user community, Granite Devices Oy or it's affiliates do not take any responsibility of the contents of this Wiki. Use information at your own risk. However, Granite Devices staff attempts to review all changes made to this Wiki and keep information trustworthy.
Without written consent, Granite Devices' Products or Intellectual Property shall not be used in situations or installations where living beings, material property, or immaterial property could be harmed by the operation, features or failures of Product. Products may only be used in a way where hazards like moving parts, electric shock, laser radiation, or fire can't be realized even if the content of this Wiki would suggest otherwise.